Appendix C: Rosemount 3300 Series with HART
®
to Modbus
®
Converter
January 2015
Rosemount 3300 Series with HART
®
to Modbus
®
Converter
Table C-13. Output Variables for Floating Point Format Code 0
Table C-14. Output Variables for Floating Point Format Code 2
Register name Register number Note
Slave 1 Status 2000
Bit information in bitfield:
Bit 0: Invalid Measurement Slave 1 PV.
Bit 1: Invalid Measurement Slave 1 SV.
Bit 2: Invalid Measurement Slave 1 TV.
Bit 3: Invalid Measurement Slave 1 FV.
Bit 14: HART bus busy (slave in burst or other master
present)
Bit 15: HTM Task not running (option not available).
Note: Bit 1-3 is set when Invalid Measurement of Slave
1 Non PV, i.e. all three bits are set simultaneously.
Slave 1 PV 2002
Primary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 0.
Slave 1 SV 2004
Secondary variable from slave 1 represented in IEEE
754 format, using Floating Point Format Code 0.
Slave 1 TV 2006
Tertiary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 0.
Slave 1 FV (QV) 2008
Fourth variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 0.
Register name Register number Note
Slave 1 Status 2100
Bit information in bitfield:
Bit 0: Invalid Measurement Slave 1 PV.
Bit 1: Invalid Measurement Slave 1 SV.
Bit 2: Invalid Measurement Slave 1 TV.
Bit 3: Invalid Measurement Slave 1 FV.
Bit 14: HART bus busy (slave in burst or other master
present)
Bit 15: HTM Task not running (option not available).
Note: Bit 1-3 is set when Invalid Measurement of Slave
1 Non PV, i.e. all three bits are set simultaneously.
Slave 1 PV 2102
Primary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 2.
Slave 1 SV 2104
Secondary variable from slave 1 represented in IEEE
754 format, using Floating Point Format Code 2.
Slave 1 TV 2106
Tertiary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 2.
Slave 1 FV (QV) 2108
Fourth variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 2.